Products: ASME
Storage Tanks
ASME Pressure Vessels
Lined and Unlined Storage Tanks
Specification
Note: items shown in parenthesis () are options.
The lined Storage Tank shall be PRECISION model number ______and shall
be a complete, pretested vessel with all required safety controls. It
shall be (horizontal) (vertical) configuration of _____" diameter by
_____" (long)(high) for _____ gallons storage. The pressure vessel
shall meet all the applicable requirements of ASME Section IV, HLW
stamped, and for (125)(150) psi design pressure, and it shall be
National Board registered. The Manufacturer shall provide the owner
with a copy of the Manufacturer's Data Report. The lined Storage Tank
shall be furnished and installed in accordance with applicable state
and local codes. Tank outer surface shall be factory painted with one
coat of industrial grade red oxide primer. Each unit is to be
manufactured by PRECISION Boilers, Morristown, TN.
OPTION: The pressure vessel shall be insulated with 2" of 3/4 pound
density fiber glass insulation or equivalent and enclosed in a sheet
steel cabinet of minimum 16 gauge thickness and painted with
industrial enamel.
OPTION: Tanks shall have _____ (Angle iron leg) (Base Ring) (Saddle)
support(s) _____ inches high as required.
OPTION: Quantity: ________ lifting lugs for handling shall be
provided.
Lining Specifications
Copper Coat™:
After complete fabrication, the tank shall be lined, by using the "thermometalization
process," with 1 00% dead soft copper to a thickness of 5-6 mils,
creating a non-ferrous corrosion-resistant protective surface. In
addition, the tank shall be equipped with Copper Coat manway cover and
Copper Coat threaded tank openings. The interior surfaces shall then
be overcoated with two (2) separate coats of Precision Seal, with a
dry film thickness of 5-6 mils each, and then force-cured in a high
temperature oven.
Precision Seal:
After complete fabrication, the tank interior shall be lined with two
(2) separate coats of Precision Seal to a minimum dry film thickness
of 5-6 mils per coat. This epoxy is then baked with individual curing
cycles in a high temperature oven.
Aluminum Silicate
Cement:
The lining shall be an aluminum silicate cement good for service
temperatures to 250°F with the same coefficient of expansion as medium
steel. The water absorption of the lining material shall not be more
than 8% of the dryweight. The cement shall be applied to a minimum
thickness of 5/8" to the interior of the Storage Tank to form a hard,
one-piece lining.